Wire Gauge Tables
AWG (American Wire Gauge) and SWG (Standard Wire Gauge) tables with diameter, cross-sectional area, and current carrying capacity for electrical wiring.
AWG Wire Sizes
| AWG | Diameter (mm) | Area (mm²) | Ampacity (A, copper) |
|---|---|---|---|
| 14 | 1.63 | 2.08 | 15 |
| 12 | 2.05 | 3.31 | 20 |
| 10 | 2.59 | 5.26 | 30 |
| 8 | 3.26 | 8.37 | 40 |
| 6 | 4.12 | 13.3 | 55 |
| 4 | 5.19 | 21.2 | 70 |
| 2 | 6.54 | 33.6 | 95 |
| 1/0 | 8.25 | 53.5 | 125 |
| 2/0 | 9.27 | 67.4 | 145 |
| 4/0 | 11.68 | 107.2 | 195 |
Metric Wire Sizes (IEC)
| Size (mm²) | Ampacity (A, copper) | Typical application |
|---|---|---|
| 1.5 | 16 | Lighting circuits |
| 2.5 | 25 | Power outlets |
| 4 | 32 | Power circuits |
| 6 | 40 | Sub-mains |
| 10 | 50 | Sub-mains, large loads |
| 16 | 65 | Distribution |
| 25 | 85 | Distribution |
| 35 | 105 | Main feeds |
| 50 | 130 | Main feeds |
| 70 | 160 | Large industrial |
| 95 | 195 | Large industrial |
| 120 | 220 | Main switchboard |
Ampacity derating
The ampacity values above are for single cables in free air at 30°C ambient. For cables in conduit, grouped with other cables, or in higher ambient temperatures, apply derating factors (typically 0.7–0.9). Always consult AS/NZS 3000 or local wiring rules for installation-specific calculations.