Reference Table

Wire Gauge Tables

AWG (American Wire Gauge) and SWG (Standard Wire Gauge) tables with diameter, cross-sectional area, and current carrying capacity for electrical wiring.

4 min readUpdated July 2026

AWG Wire Sizes

AWGDiameter (mm)Area (mm²)Ampacity (A, copper)
141.632.0815
122.053.3120
102.595.2630
83.268.3740
64.1213.355
45.1921.270
26.5433.695
1/08.2553.5125
2/09.2767.4145
4/011.68107.2195

Metric Wire Sizes (IEC)

Size (mm²)Ampacity (A, copper)Typical application
1.516Lighting circuits
2.525Power outlets
432Power circuits
640Sub-mains
1050Sub-mains, large loads
1665Distribution
2585Distribution
35105Main feeds
50130Main feeds
70160Large industrial
95195Large industrial
120220Main switchboard

Ampacity derating

The ampacity values above are for single cables in free air at 30°C ambient. For cables in conduit, grouped with other cables, or in higher ambient temperatures, apply derating factors (typically 0.7–0.9). Always consult AS/NZS 3000 or local wiring rules for installation-specific calculations.