Temperature Sensors

Temperature is one of the most measured variables in process plants. Learn about RTDs, thermocouples, thermistors, and how to select the right sensor.

6 min readUpdated July 2026

Main Types of Temperature Sensors

  • RTD (Resistance Temperature Detector): A precision wire winding (usually platinum) whose resistance changes with temperature. Very accurate and stable. Most common type: Pt100 (100 ohms at 0 degrees C). Range: -200 to 600 degrees C.
  • Thermocouple: Two dissimilar metal wires joined at a junction. The junction generates a small voltage proportional to temperature. Less accurate than RTD but can handle much higher temperatures. Range: -200 to 1,800 degrees C depending on type.
  • Thermistor: A semiconductor whose resistance changes dramatically with temperature. Very sensitive but non-linear and limited temperature range. Used for low-cost, high-sensitivity applications.
  • Infrared (pyrometer): Measures temperature by detecting infrared radiation. Non-contact. Used for moving surfaces, high temperatures, or where contact is impractical.

RTD vs Thermocouple

FeatureRTD (Pt100)Thermocouple
Accuracy+/- 0.1 to 0.5 degrees C+/- 1 to 5 degrees C
StabilityExcellent (drifts less than 0.1 degrees C/year)Good (drifts 1 to 5 degrees C/year)
Temperature range-200 to 600 degrees C-200 to 1,800 degrees C
Response timeSlower (1 to 10 seconds)Faster (0.1 to 5 seconds)
CostHigherLower
Lead wire effect3-wire or 4-wire requiredCompensation cable required
Best forProcess temperature, accuracy-criticalHigh temperature, harsh environments

Installation Considerations

  • Thermowell: A protective sleeve inserted into the process. The sensor slides into the thermowell. Allows sensor replacement without shutting down the process. But adds thermal lag and reduces accuracy.
  • Immersion depth: The sensor should be immersed at least 5 to 10 pipe diameters or sufficiently past the pipe wall to avoid measuring the wall temperature rather than the fluid temperature.
  • Lead wire routing: Keep sensor leads away from power cables to avoid electromagnetic interference. Use shielded cable for RTDs.
  • Junction type: RTDs can be 2-wire, 3-wire, or 4-wire. 3-wire compensates for lead resistance. 4-wire is most accurate. Always match the transmitter to the sensor wiring type.

Use the correct extension cable for thermocouples

Thermocouples generate a voltage at the junction. If you connect with standard copper wire, you create a second junction at the connection point, adding an unwanted voltage. Always use thermocouple extension cable made of the same material as the thermocouple. Using the wrong cable is a common source of temperature measurement errors.

Tip: Calibrate temperature sensors annually using a dry block calibrator. Compare the sensor reading to the calibrator at three points (low, mid, high). RTDs should be within +/- 0.5 degrees C. Thermocouples within +/- 2 degrees C. Replace sensors that drift outside specification.