MCC Explained (Motor Control Centre)

A Motor Control Centre (MCC) houses motor starters, protection devices, and controls in a centralised panel. Learn about MCC components, layout, and maintenance.

6 min readUpdated July 2026

What is an MCC?

A Motor Control Centre (MCC) is a panel or assembly of panels containing the starters, protection devices, and control circuits for multiple motors. It centralises motor control, protection, and monitoring in one location, typically near the motors it controls.

An MCC provides: power distribution to motors, short-circuit and overload protection, motor starting control (DOL, star-delta, soft starter, or VFD), local control (start/stop buttons, indicators), and interface with plant control systems (PLC, SCADA).

Components in an MCC Bucket

  • Circuit breaker or fuses: Short-circuit protection. Disconnects the motor from the supply on a fault.
  • Contactor: An electromechanical switch that starts and stops the motor. Controlled by the start/stop circuit or PLC.
  • Overload relay: Thermal or electronic protection that trips when motor current exceeds the rated value for too long. Protects against sustained overloading.
  • Control transformer: Steps down the supply voltage to a safe control voltage (typically 24V DC or 240V AC) for the control circuit.
  • VFD or soft starter: Where variable speed or soft starting is required, the VFD or soft starter replaces or supplements the contactor.
  • Indicators and controls: Running/stopped indicators, fault indicators, local start/stop buttons, ammeter.

Maintenance

  • Thermal imaging: Scan the MCC with an infrared camera. Hot spots indicate loose connections, overloaded components, or failing contactors.
  • Torque check: Annually, torque all power connections to spec. Loose connections cause overheating and fire.
  • Clean interior: Dust and dirt in the MCC can cause tracking and short circuits. Vacuum (don't blow) annually.
  • Check contactors: Inspect contactor tips for pitting and wear. Replace contacts if severely worn. Listen for buzzing (indicates dirty armature or failing coil).
  • Test overload relays: Verify the overload trip point matches the motor full-load current. Test the trip function.
  • Check door seals and gaskets: Intact seals prevent dust and moisture ingress. Replace damaged gaskets.
  • Verify labelling: Every bucket, device, and wire should be clearly labelled. Missing or incorrect labels cause dangerous errors during maintenance.

Arc flash safety

MCCs contain energised high-current equipment. Arc flash can cause severe burns and death. Only qualified electricians should open or work on MCCs. Follow arc flash safety procedures: wear appropriate PPE, use insulated tools, de-energise where possible, and follow lockout/tagout. Never work on an energised MCC without proper training and authorisation.

Tip: Schedule an annual thermal imaging survey of the MCC. Hot spots at connections, breakers, or contactors appear clearly on a thermal image. Fixing loose connections early prevents failures, fires, and arc flash incidents.