Level Transmitters
Level measurement is essential for tanks, vessels, and boilers. Learn the different technologies, how they work, and how to select the right level transmitter.
Types of Level Measurement
- Differential pressure (DP): Measures the hydrostatic pressure at the bottom of the tank. Pressure = liquid height x density x gravity. Simple, reliable, and works for most liquids. Needs to account for liquid density.
- Ultrasonic: Sends an ultrasonic pulse from the top of the tank and measures the time for the echo to return. Non-contact. Good for corrosive or dirty liquids. Affected by vapour, foam, and turbulence.
- Radar (guided wave and non-contact): Uses radar pulses instead of ultrasonic. Not affected by vapour or density changes. More expensive than ultrasonic but more reliable in difficult applications.
- Float and cable: A float on the liquid surface is connected by a cable to a measuring mechanism. Simple and direct. Mechanical, so subject to wear.
- Capacitance: Measures the capacitance between a probe and the tank wall. Liquid changes the dielectric, changing capacitance. Good for non-conductive liquids. Affected by coating and buildup.
- Hydrostatic pressure: A pressure transmitter at the bottom of the tank measures the pressure, which is proportional to liquid height. Same principle as DP but uses a single pressure measurement.
Boiler Level Measurement
Boiler drum level is one of the most critical measurements in a steam plant. Too low: tubes overheat and rupture. Too high: water carryover damages equipment. Two methods are used:
- Differential pressure: A DP cell measures the difference between the water column (reference leg) and the drum pressure. Accurate but affected by density changes (at different pressures, water density changes, affecting the calibration).
- Conductivity (boiler gauge glass): A series of electrodes at different heights detect water level by conductivity. Simple, direct, and reliable. Used for level indication and low-water alarm.
Boiler level is safety-critical
Every boiler must have at least two independent level indications. The primary low-water cutoff must be independent of the level control transmitter. Test the low-water cutoff weekly. If it fails, the boiler can run dry, causing catastrophic tube failure within minutes.
Common Problems
- Density changes: DP level measurement assumes constant liquid density. If temperature or composition changes, the reading drifts. Compensate with temperature measurement.
- Foam and turbulence: Ultrasonic and radar meters can give false readings if the liquid surface is foamy or turbulent. Use guided wave radar for better performance in these conditions.
- Coating and buildup: Capacitance and float-type meters can be affected by material buildup on the probe or float. Clean regularly.
- Vapour interference: Ultrasonic meters can be affected by vapour above the liquid. Radar is less affected.
- Reference leg temperature: For boiler DP level measurement, the reference leg (constant head) must be at a known temperature. If it cools, the water density changes, causing level error. Insulate the reference leg.
Tip: For critical level measurements (boiler drum, chemical tanks), install two different types of level transmitter. If they disagree, you know something is wrong. Two independent measurements are always better than one, especially for safety-critical levels.