How-To Guide

How to Size a Steam Trap

Oversized traps cycle wastefully; undersized traps back up condensate. Learn the correct sizing procedure — from calculating condensate load to selecting the right orifice.

8 min readUpdated July 2026

Why Sizing Matters

A correctly sized steam trap discharges condensate as fast as it forms, without passing live steam. An oversized trap opens and closes too frequently (wearing the seat) and may pass steam on each cycle. An undersized trap cannot keep up with the condensate load, causing waterlogging, reduced heat transfer, and water hammer.

The two things you need

Sizing a steam trap requires two numbers: (1) the condensate load in kg/hr, and (2) the differential pressure across the trap in bar. Get these right and the manufacturer's sizing chart does the rest.

Step 1: Determine the Condensate Load

The condensate load is the amount of steam that condenses in your application. Calculate it based on the equipment type:

ApplicationHow to calculate load
Heat exchangerQ (kW) × 1.6 = kg/hr condensate (latent heat ≈ 2100 kJ/kg)
Pipe warm-up (startup)Calculate from pipe mass, specific heat, and warm-up time
Tracing lineUse manufacturer's table — typically 0.3–1.0 kg/hr per metre
Drip leg on steam mainTypically 1–5% of steam flow under running conditions
Process heaterQ (kW) ÷ latent heat (kJ/kg) × 3600 = kg/hr

Tip: Always check the manufacturer's data for the specific equipment. For warm-up loads (startup), the condensate load can be 3–5× the running load — size for the higher of the two, or use a trap with adequate startup capacity.

Step 2: Apply a Safety Factor

The calculated load is the minimum. Apply a safety factor to account for load variations, startup surges, and operating pressure fluctuations.

ApplicationSafety factor
Continuous process (heat exchanger, heater)1.5× calculated load
Batch process (alternating on/off)2.0× calculated load
Steam main drip leg2.0–3.0× calculated load
Startup / warm-up loads3.0× calculated load

Don't oversize without reason

A safety factor that is too high causes the trap to cycle too fast and wear prematurely. Use the appropriate factor for your application, not a blanket 3× on everything.

Step 3: Determine the Differential Pressure

The differential pressure (ΔP) is the pressure difference across the trap. It is the upstream steam pressure minus the downstream back pressure.

  1. Identify the upstream steam pressure at the trap inlet (Ps).
  2. Identify the downstream pressure (Pb) — this is the condensate return line pressure or atmospheric pressure if discharging to drain.
  3. Calculate ΔP = Ps − Pb.
  4. If the condensate is lifted vertically after the trap, subtract 0.1 bar per metre of lift from ΔP.
  5. Verify that ΔP is positive — if the back pressure exceeds the upstream pressure, the trap cannot discharge.

Startup vs running pressure

At startup, the steam pressure is lower than operating pressure because the line is still warming. If the trap needs to discharge condensate at startup (it usually does), verify that the trap can operate at the lower startup differential pressure.

Step 4: Select the Trap Type

ApplicationRecommended trap type
Mainline drip legsThermodynamic (TD)
Steam tracingThermodynamic or thermostatic
Heat exchangers (steady load)Float and Thermostatic (F&T)
Heat exchangers (variable load)Float and Thermostatic (F&T) with modulating valve
Air venting at startupThermostatic (separate air vent)
Superheated steam linesThermodynamic (only type that handles superheat)

Step 5: Select the Orifice / Capacity

Using the manufacturer's capacity chart for your chosen trap type, find the model whose discharge capacity at your ΔP exceeds the safety-factored condensate load.

  1. Find the manufacturer's capacity table for the trap type you selected.
  2. Locate your differential pressure (ΔP) in the pressure column.
  3. Read across to find the capacity in kg/hr at that ΔP.
  4. Select the trap model whose capacity exceeds your safety-factored load.
  5. If the capacity is well above your load, consider a smaller orifice to reduce cycling wear.
ExampleValue
Calculated condensate load200 kg/hr
Safety factor1.5×
Required capacity300 kg/hr
Differential pressure4 bar
Selected trap capacity at 4 bar ΔP380 kg/hr
ResultAdequate — trap exceeds required capacity

Common Sizing Mistakes

  • Sizing for startup only: Startup loads are much higher than running loads. If you size for startup, the trap will be oversized for normal operation and cycle too fast. Size for running load with startup capacity as a check.
  • Ignoring back pressure: If the condensate return line has back pressure, the effective ΔP is reduced. Failing to account for this results in a trap that cannot discharge at full load.
  • Ignoring lift: Lifting condensate vertically after the trap reduces the effective ΔP by 0.1 bar per metre. If the lift is too high, the trap will stall.
  • Using the pipe size for the trap size: The trap connection size is NOT the same as the trap capacity. A 15mm trap can have a much larger capacity than a 25mm trap of a different type. Always size by capacity, not by pipe connection.