Checklist

Daily Boiler Inspection Checklist

A comprehensive daily inspection checklist for boiler operators — covering water treatment, blowdown, controls, combustion, and safety devices.

5 min readUpdated July 2026

Water Treatment

  • Test boiler water TDS: Take a sample and check conductivity. Adjust blowdown if TDS exceeds the limit (typically 3000–3500 ppm).
  • Test feedwater hardness: Verify zero hardness. If hardness is detected, check the softener and regenerate if needed.
  • Check pH: Boiler water pH should be 10.5–12.0. Adjust chemical dosing if out of range.
  • Check chemical dosing: Verify dosing pumps are operating and chemical levels are adequate.
  • Test dissolved oxygen: Feedwater oxygen should be below 0.02 ppm. Check deaerator operation.

Blowdown

  • Bottom blowdown: Perform bottom blowdown once per shift (3–5 second bursts × 2–3 times) to remove sludge.
  • Surface blowdown: Check TDS controller operation. Verify continuous blowdown valve position.
  • Check blowdown temperature: Verify blowdown water is cooled in the blowdown tank before discharge.

Controls and Safety Devices

  • Test low-water cutoff: Blow down the float column and verify the burner shuts down. Record the test.
  • Check water level gauge: Blow down the gauge glass to verify it's clear. Verify level matches remote indication.
  • Verify safety valve: Visual inspection — check for leaks. Gently lift the test lever if fitted (only when boiler is at >75% operating pressure).
  • Check pressure gauge: Verify pressure is stable and within normal range. Tap the gauge to verify the needle isn't stuck.
  • Check combustion air pressure switch: Verify it trips the burner when air is insufficient (test during shutdown).

Combustion

  • Observe flame: Check flame through the inspection port — should be stable, blue (gas), not impinging on refractory.
  • Check flue gas temperature: Record the stack temperature. An increase indicates fouled tubes.
  • Check fuel pressure: Verify fuel pressure is within the normal range.
  • Listen for unusual noises: Humming, rumbling, or pulsing indicates combustion problems.

General

  • Check for leaks: Walk around the boiler and check all flanges, valves, and fittings for water, steam, or fuel leaks.
  • Check motor temperatures: Feel the feedwater pump, fan, and fuel pump motors — should be warm, not hot.
  • Record all readings: Complete the boiler log: pressure, temperature, water level, fuel consumption, steam flow, blowdown events.
  • Check alarms: Verify the alarm panel is clear of active alarms.