Guide

Cooling Tower vs Chiller: What's the Difference?

Cooling towers and chillers are both used for cooling, but they work on completely different principles. This guide explains the difference, when to use each, and how they work together in large HVAC systems.

7 min readUpdated July 2026

The Fundamental Difference

  • Chiller: A machine that uses a refrigeration cycle (compressor, condenser, expansion valve, evaporator) to produce chilled water — typically at 6–7°C. The chilled water is circulated through cooling coils in air handling units to cool building air. Chillers actively remove heat using mechanical refrigeration.
  • Cooling tower: A device that cools water by evaporation. Warm water from a process or condenser is sprayed through air, and some of it evaporates, cooling the remaining water to near the wet bulb temperature. Cooling towers don't use refrigeration — they use the natural cooling effect of evaporation. Cooling towers produce water at approximately 27–30°C (the 'condenser water' temperature).

Comparison

CharacteristicChillerCooling Tower
Cooling methodMechanical refrigeration (vapour compression)Evaporative cooling (water + air)
OutputChilled water at 6–7°CCondenser water at 27–30°C
Minimum temperatureCan cool below wet bulbCan only cool to wet bulb + 3°C
Energy consumptionHigh (compressor power)Low (fan and pump only)
Capital costHighLow to moderate
Water consumptionNone (closed loop)High (evaporation + blowdown)
MaintenanceRefrigeration specialist requiredWater treatment and cleaning
Legionella riskNoneHigh (must manage)
SizeCompactLarge (requires roof or ground space)

When to Use Each

The choice depends on the required water temperature and the application:

  • Use a chiller when you need cold water (6–7°C) for air conditioning, process cooling, or dehumidification
  • Use a cooling tower when you need to reject heat from a process or condenser and the water temperature only needs to be near the wet bulb (27–30°C)
  • Use both together in a water-cooled chiller system: the chiller produces cold water, and the cooling tower rejects the chiller's condenser heat to the atmosphere
  • Use only a cooling tower for 'free cooling' in mild climates — when the outdoor wet bulb is low enough, the tower can cool water directly without running the chiller

How They Work Together

In a typical large-building HVAC system, the chiller and cooling tower work as a team:

  1. The chiller produces chilled water (6–7°C) and circulates it to air handling units
  2. The AHUs use the chilled water to cool building air
  3. The warm chilled water returns to the chiller evaporator to be re-cooled
  4. The chiller's condenser rejects heat to condenser water (27–35°C)
  5. The warm condenser water is pumped to the cooling tower
  6. The cooling tower cools the condenser water by evaporation (to 27–30°C)
  7. The cool condenser water returns to the chiller condenser to absorb more heat

Key insight: Water-cooled chillers (with cooling towers) are approximately 20–30% more energy-efficient than air-cooled chillers, because the condenser can reject heat to water at a lower temperature than air. However, they require more maintenance (water treatment, Legionella management) and consume water.

Digitise your maintenance with PlantLogica

PlantLogica connects to your equipment sensors via PLC, schedules preventive maintenance, logs work offline by voice in the field, and uses AI to predict failures before they happen.