Guide

Chiller Low Suction Pressure: Causes & Troubleshooting

Low suction pressure on a chiller indicates the evaporator is too cold or refrigerant flow is insufficient. Learn the causes — from low refrigerant to faulty expansion valves — and how to diagnose each.

8 min readUpdated July 2026

What is Low Suction Pressure?

Suction pressure is the refrigerant pressure at the compressor inlet. It corresponds to the evaporator temperature — low suction pressure means the evaporator is colder than it should be, or the refrigerant flow is insufficient. Left uncorrected, low suction pressure can cause compressor damage from low refrigerant density (the compressor starves for refrigerant), oil migration (oil doesn't return to the compressor), and freeze damage (the evaporator freezes).

Causes

  • Low refrigerant charge: The most common cause. A refrigerant leak reduces the amount of refrigerant available to fill the evaporator. The expansion valve can't supply enough refrigerant, and suction pressure drops. Fix: find and repair the leak, then recharge to the correct charge.
  • Faulty expansion valve: If the thermostatic expansion valve (TXV) or electronic expansion valve (EEV) is stuck closed or underfeeding, insufficient refrigerant enters the evaporator. Fix: check the superheat setting, verify the sensor bulb is correctly attached, and replace the valve if faulty.
  • Restricted liquid line: A blockage in the liquid line (filter drier, solenoid valve, or kinked pipe) restricts refrigerant flow to the expansion valve. Fix: check the temperature drop across the filter drier — if there's a drop, the drier is blocked and needs replacement.
  • Low chilled water flow: If the chilled water flow through the evaporator is too low, the refrigerant absorbs less heat and the evaporator temperature drops, lowering suction pressure. Fix: check the chilled water pump, strainer, and balancing valves.
  • Evaporator fouling: Scale or biofouling on the evaporator tubes reduces heat transfer. The refrigerant doesn't absorb enough heat and the suction pressure drops. Fix: clean the evaporator tubes.
  • Cold chilled water setpoint: If the setpoint is set below the design, the chiller tries to achieve an evaporator temperature that's too low. Fix: verify the setpoint is correct (typically 6–7°C supply water).
  • Compressor unload: If the compressor unloads (part-load operation) but the expansion valve doesn't reduce refrigerant flow proportionally, the evaporator overfeeds and then starves cyclically. Fix: check the capacity control and expansion valve coordination.

Diagnostic Steps

  1. Check superheat: Measure the suction line temperature and pressure. Calculate superheat = actual suction gas temp − saturated temp at suction pressure. Normal: 5–8°C. High superheat indicates the expansion valve is underfeeding (low charge or restricted valve). Low superheat indicates overfeeding (faulty valve or oversized port).
  2. Check subcooling: Measure the liquid line temperature and pressure. Calculate subcooling = saturated temp at liquid pressure − actual liquid temp. Normal: 5–10°C. Low subcooling suggests low charge; high subcooling suggests a liquid line restriction.
  3. Check chilled water delta-T: Measure the chilled water inlet and outlet temperatures at the evaporator. A larger than design delta-T indicates low flow; a smaller delta-T indicates high flow or evaporator fouling.
  4. Check the filter drier: Measure the temperature before and after the liquid line filter drier. A temperature drop of more than 0.5°C indicates a blocked drier.
  5. Leak test: If low charge is suspected, use an electronic leak detector or UV dye to find the leak. Check all joints, Schrader valves, and the evaporator and condenser tubes.

Consequences of Ignoring

  • Evaporator freezing — if the evaporator temperature drops below 0°C, the chilled water can freeze, rupturing tubes
  • Compressor damage — low suction pressure means low refrigerant density at the compressor, which reduces cooling of the motor windings
  • Oil migration — insufficient refrigerant velocity in the suction line means oil doesn't return to the compressor, causing bearing failure
  • Capacity loss — the chiller can't produce the required cooling, causing the chilled water temperature to rise

Digitise your maintenance with PlantLogica

PlantLogica connects to your equipment sensors via PLC, schedules preventive maintenance, logs work offline by voice in the field, and uses AI to predict failures before they happen.