Boiler Safety Valves

Safety valves are the last line of defence against boiler overpressure. Learn how they work, sizing requirements, testing procedures, and why they must never be tampered with.

6 min readUpdated July 2026

Purpose of Safety Valves

A boiler safety relief valve is designed to open automatically when boiler pressure exceeds the maximum allowable working pressure (MAWP), discharging excess steam to prevent a catastrophic explosion. It is the most important safety device on the boiler.

If all controls fail, all alarms are ignored, and pressure continues to rise, the safety valve is the final barrier between normal operation and a boiler explosion. It must work every time, without exception.

Never tamper with a safety valve

Never adjust, wire shut, or block a safety valve. Never increase the set pressure above the boiler's MAWP. Doing so is a criminal offence in most jurisdictions and risks catastrophic explosion. If a safety valve is leaking or lifting at the wrong pressure, have it serviced by a certified technician.

How Safety Valves Work

A spring-loaded safety valve stays closed until steam pressure exceeds the spring force. When pressure reaches the set point, the valve pops open fully (not gradually). It remains fully open until pressure drops to a predetermined reseat pressure (typically 4 to 6% below set pressure).

The pop action is achieved by a special seat design that creates a larger effective area once the valve lifts, requiring a pressure drop to reseat. This prevents the valve from chattering open and closed near the set point.

Sizing Requirements

  • Capacity: The safety valve must be able to discharge the full steam generating capacity of the boiler at the MAWP. If the valve is too small, pressure can continue to rise above the MAWP.
  • Number: Most codes require at least two safety valves on boilers above a certain capacity. This provides redundancy.
  • Set pressure: At least one safety valve must be set at or below the MAWP. Others may be set up to 3% above MAWP.
  • Discharge piping: Must be sized to handle the full discharge flow without excessive back pressure. Must route to a safe location where no one can be injured by escaping steam.

Testing and Certification

  1. Pop test (annually): With the boiler operating, slowly close the main steam stop valve to raise pressure until the safety valve lifts. Verify it opens at the set pressure and reseats correctly.
  2. Gag test (if lift is not possible): A certified technician tests the valve using a hydraulic lift assist device to verify the spring tension without full blowdown.
  3. Certification: Safety valves must be certified by an authorised testing authority. In Australia, follow AS 1271 or ASME Section I, depending on the boiler standard applied.
  4. Record keeping: Maintain records of all safety valve tests, servicing, and certifications. PlantLogica's compliance reporting module can track these automatically.

If a safety valve lifts, investigate

A safety valve lifting means the pressure control system failed. Do not simply reset and continue. Investigate the cause: pressure controller failure, modulating valve stuck closed, burner stuck on high fire. Fix the root cause before returning to normal operation.