AHU Maintenance Checklist: Air Handling Unit Guide

A complete maintenance checklist for Air Handling Units (AHUs) — covering filters, coils, fans, dampers, and controls. Daily, monthly, and annual tasks to keep your AHU running efficiently.

8 min readUpdated July 2026

Daily Checks

  • Check supply and return air temperatures — compare to setpoint
  • Listen for unusual noise from the fan or motor
  • Check for visible air leaks at the AHU casing and duct connections
  • Verify the condensate drain is flowing (during cooling operation)
  • Check the control panel for alarms or fault indicators

Monthly Maintenance

  • Check and replace air filters — measure pressure drop; replace at manufacturer's recommended differential (typically 250 Pa)
  • Inspect the cooling and heating coils for dirt and biofouling — clean if necessary
  • Check the fan belt for tension and condition — adjust or replace
  • Inspect the fan and motor bearings — listen with an ultrasonic stethoscope
  • Check the condensate drain pan — clean if dirty, verify the drain is not blocked
  • Inspect the dampers — verify they move freely and position correctly
  • Check the motor amperage — compare to nameplate FLA
  • Inspect the AHU casing for air leaks — seal with appropriate gasket or sealant
  • Clean the temperature and humidity sensors — dust on sensors causes inaccurate readings

Annual Maintenance

  1. Replace all air filters: Use the correct filter class (G4, F7, F9, etc.) for the application. Consider upgrading to higher-efficiency filters if air quality is an issue.
  2. Deep clean the coils: Use a coil cleaner and low-pressure water. Clean both the air side and the water/refrigerant side (if accessible). Brush the fins straight if bent.
  3. Service the fan: Check the impeller for dirt buildup and balance. Inspect the housing for corrosion. Lubricate bearings (if not sealed). Check the belt condition and alignment.
  4. Service the motor: Check bearings, winding resistance (megger test), and wiring connections. Verify the motor cooling fan is clean.
  5. Inspect and service dampers: Clean and lubricate the damper linkages. Verify the actuator operates smoothly. Check the damper blades for damage and seal degradation.
  6. Clean the condensate system: Remove and clean the condensate drain pan. Flush the drain line. Check the trap for proper operation.
  7. Calibrate sensors: Calibrate the temperature, humidity, and pressure sensors against a reference instrument.
  8. Inspect the casing and insulation: Check for air leaks, damaged insulation, and corrosion. Seal leaks and repair insulation.
  9. Check the control system: Verify all control sequences operate correctly — start/stop, temperature control, damper control, safety interlocks.
  10. Performance test: Measure the supply airflow, temperature, and static pressure. Compare to design values and previous year's readings.

Common Problems

ProblemLikely Cause
Reduced airflowDirty filter, dirty coil, belt slip, damper closed
Insufficient coolingDirty coil, low refrigerant, low chilled water flow, valve closed
Water leakage from AHUBlocked condensate drain, cracked drain pan, frozen coil
High motor amperageDirty filter, dirty coil, belt too tight, bearing failure
Noise/vibrationWorn bearings, belt issue, impeller imbalance, loose components
Temperature not reaching setpointSensor error, valve stuck, control issue, insufficient capacity